SW1138 IR3-109/1CZ IR3 Flame Detector
Produktet er ikke tilgjengelig fra nettsiden
| Nettovekt (kg) | 1 |
|---|
The SENSE-WARE IR3 flame detectors utilizes a microprocessor for sophisticated electronic signal analysis. The Infrared sensors must exceed their alarm threshold balance to initiate a fire alarm. The triple IR flame detector uses an additional alarm criterion: the analysis of the flame flicker-frequency. The infrared IR3 flame detector has good false alarm rejection capabilities, including Arc Welding (> 3m), chopped sunlight or halogen lights but is still able to detect a real fire at the same time. To prevent unwanted alarms, the dynamic delay time for an alarm is 4-8 seconds depending on the size and or the distance to the flames. The triple IR flame detector is suitable for the detection light- and heavy Hydrocarbon fires, in fact, every yellow to red flame that emits Carbondioxide will be detected. A self-test is performed every hour to make sure the sensor and electronics operate well. A Test Lamp is available for regular inspections and end-to-end testing.
Automatic sensor test
Operating temp.: -40 to +70°C (in Safe Area’s only
GRP housing
Relay output for Alarm and Fault
CPR/EN54-10 certified
Tlbehør: 2401228 SM21 BRAKETT